(i) clear pathways of minimum seventy five centimetre in width with hand rails for roof access and
emergency exit shall be provided for roof top system;
(ii) there shall be clear pathways, walkways between the rows or columns of solar panels which is
necessary for cleaning and maintenance;
(iii) cables shall be laid in trenches for ground based photovoltaic installation;
(iv) ground mounted solar installations shall be protected by fencing or other means not less than 1.8 metre
in height so as to prevent unauthorised entry;
(v) disconnection switches or circuit breakers provided in combiner boxes to disconnect the
photovoltaic system from all other conductors of the system shall be located at a readily accessible location;
(vi) three phases on the alternating current side, and positive and negative conductor on the direct current
side shall be marked and identified with different colours;
(vii) inverter unit for solar photovoltaics shall be installed in the periphery of the building and as near as
the solar panel:
Provided that the direct current cable shall be ultraviolet protected or routed through ultraviolet
protected pipe;
(viii) there shall be a manual disconnection switch to isolate the system from grid and shall be situated
outside the alternating current combiner box; and
(ix) protection shall be deployed (for both input and output) on site for overload, surge current, surge
voltage, short circuit, high temperature, over voltage, under voltage and over frequency, under frequency,
reverse polarity and lightning.